Description
 
The cabinet includes one compartment. The cabinet cooling uses air conditioner and fans, to ensure the equipments operate normally at stable temperature range, so as to make the service life of the equipments much longer and their performance more stable.
 

Technical Parameters
 

Item  Type  Technical Parameter
StructureDimensionExternal Dimension H*W*D  2000*800*800mm
Internal Dimension H*W*D   1800*700*700mm
Layout One compartment
Equipment Installation Method19" rack
Door With one front door, with special lock for 
outdoor cabinet (support padlock) 
Material Galvanized steel; double wall, thickness of outer plate: 1.5mm,
thickness of inner plate: 0.8mm.
Heat InsulationThere are heat insulation between inner wall and outer wall. 
The insulation material is 20mm PEF.
Structure Welded
Ingress ProtectionIP55
Temperature ControlCooling 1500W, AC220V air conditioner + 48V to 220V inverter; 
and DC48V fans 
LightingLED lamp48V LED lamps, when the door is open,
 the LED lamp will turn on; 
when the door is closed, the LED lamp will turn off.
Temperature TemperatureWorking Temperature: -40°C ~ +55°C
Storage Temperature: -50°C ~ + 70°C
Transport Temperature: -50°C ~ +70°C
HumidityRelative Humidity5% ~ 100%
PressureAir Pressure 62kpa ~ 101kpa (similar to 0m ~ 5000m altitude)
Radiation Intensity Solar Radiation Intensity1120 × (1±5%)W/m2

 

Lead Acid Battery Specs
 
The cabinet can hold maximum 3 battery strings ( each battery string is 48V 100AH).
 
(1) When the air conditioner is "on":
 
Battery Capacity = 3h*40A/0.7=171Ah
 
"3h" is backup time, "40A" is (equipments + air conditioner) load, "0.7" is battery remaining
 
Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).
 
(2) When the air conditioners are "off":
 
Battery Capacity = 6h*20A/0.7=171Ah
 
"6h" is backup time, "20A" is equipments load, "0.7" is battery remaining
 
Our suggestion: use 2 battery strings ( each battery string is 48V 100AH).
 

Accessories List
 

No. ItemQuantityUnit Specs
1Outdoor Telecom Cabinet1Set External Dimension H*W*D  2000*800*800mm
                               
2Air Conditioner1SetCooling capacity: 1500W,  Power Supply: 220V; 
Model: TC06-150JFH/01
3Embedded Telecom Power System1Set1U, 19", 3000W, DC48V,60A
4Inverter1Set48V to 220V (for air conditioner power supply)
5Fan2Set12038, DC48V, START WORK AT 35°C
6Power Distribution1SetGRADE B LIGHTNING PROOF                                 
AC INPUT: 63A/2P *1;                                             
AC OUTPUT: 16A/1P*4;                   
DC OUTPUT: 16A/1P*4
7Lead Acid Battery8Set12V, 100AH, Model: SP12-100
8Temperature and Humidity Sensor1PC
9Environment Monitoring Unit1Set2U
10Door Sensor2PC 
11Water Sensor1PC
12Smoke Sensor1

13LED Lamp1PCDC48V
14Package1Set Wooden Case


  • Contact Us

    Hangzhou Fengtu Import & Export Co.,Ltd
    Add:Room 706, Building 1, Jiangnan Mingcheng, No. 818 North Shixin Road, Xiaoshan District, China
    Tel:+86-571-82310975
    Fax:+86-571-82310975
    Mobile:+86-18667160915
    E-mail:stevexue@ftprefabhouse.com

  • Categories
  • Copyright © Hangzhou Fengtu Import & Export Co.,Ltd All Rights Reserved.